The fancoil FCY concept extends to non residential applications where the demands of thermal capacity, robustness and reliability requirements prevail over process requests and the need for customization.
The FCY range is presented as a big solution in terms of thermal capacity, which allows the designer to find in only one device the performance of several conventional fancoils. This product range is an economical and reliable solution suitable for several sectors, ranging from industry to commerce or offices.

This product range offers reliable solutions from 4000 to 13000 m3/h, mainly for secondary air handling. Its possible compatibility with hydronic and direct expansion systems makes it a versatile product, suitable for any installation, regardless of the type of production.
The FCY series can be an integral solution in itself, as the regulation of the fan working point and control system provide the unit a complete autonomy in normal operation mode.
FCY range features stem from a culture of reliable product development, reflecting the know-how of years of experience and knowledge of HVAC market in a series that stands out for its robustness and good performance

Robustez
The components of the FCY range have been widely tested in diverse applications of HVAC market, a degree of experience that guarantees its robustness and durability over time.

Adaptability
The wide range of existing models, different configurations available, and the possibility of integration in hydronic and direct expansion systems make FCY a versatile solution within its range of application.

Economy
The FCY series has been fully optimised, both in terms of design and component selection. This has resulted in a range that stands out for its high performance-price ratio.

Comprehensive Solution
FCY product range offers a comprehensive solution for customer and installer. The possibility of regulating the operating point of the fan and integrated thermostat control make this a comfortable and compact solution.

Technical Characteristics
FCY | 018 | 025 | 030 | 040 | 045 | 055 | 075 | |||||
Cooling Capacity * | kW | 19 | 28 | 32 | 41 | 60 | 66 | 81 | ||||
Heating Capacity ** | kW | 51 | 64 | 72 | 93 | 132 | 143 | 175 | ||||
Heating Capacity *** | kW | 25 | 32 | 36 | 46 | 65 | 71 | 87 | ||||
Weight | kg | 130 | 140 | 150 | 230 | 297 | 317 | 365 | ||||
Exchanger water/air | ||||||||||||
Frontal Area | m² | 0,550 | 0,638 | 0,696 | 0,84 | 1,098 | 1,098 | 1,338 | ||||
Nº Rows…Fins/m | 4...476 | 4...500 | 4...500 | 4...500 | 6...476 | 6...476 | 6...476 | |||||
Manifold | pulg | 1 1/4" | 1 1/4" | 1 1/4" | 1 1/2" | 2" | 2" | 2" | ||||
Water Volume | l | 5,5 | 6,4 | 7 | 8,4 | 16,5 | 16,5 | 20,2 | ||||
Water Flow (Cold Coil) | l/h | 2900 | 4800 | 5700 | 7000 | 10100 | 11300 | 13400 | ||||
Water Flow (Heat Coil) ** | l/h | 4500 | 5600 | 6300 | 8100 | 11600 | 12500 | 15300 | ||||
Water Flow (Heat Coil) *** | l/h | 4400 | 5500 | 6200 | 8000 | 11400 | 12300 | 15100 | ||||
Pressure Drop Water (Cold Coil) | kPa | 7,6 | 17,2 | 20,4 | 30,4 | 16,4 | 20 | 31,8 | ||||
Pressure Drop Water (Heat Coil)** | kPa | 13,6 | 18 | 18,9 | 34,5 | 17,8 | 20,5 | 34,8 | ||||
Pressure Drop Water (Heat Coil)*** | kPa | 14,4 | 19,1 | 20,1 | 36,8 | 19 | 21,9 | 37,3 | ||||
Fan | ||||||||||||
Air Flow | m³/h | 4300 | 5364 | 6084 | 7884 | 9504 | 10476 | 12708 | ||||
Quantity | ud. | 2 | 2 | 2 | 2 | 2 | 2 | 2 | ||||
Maximum External Pressure | Pa | 150 | 150 | 165 | 220 | 300 | 215 | 210 | ||||
Motor | ||||||||||||
Quantity | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |||||
Installed Motor-Power | kW | 1,1 | 1,5 | 2,2 | 3 | 3 | 4 | 4 | ||||
Air Filter | ||||||||||||
Quantity | 2 | 2 | 2 | 2 | 1 | 2 | 1 | 2 | 1 | 3 | 1 | |
Wide x Heigth | mm | 590x490 | 590x540 | 590x590 | 590x590 | 290x590 | 590x590 | 690x590 | 590x590 | 690x590 | 590x590 | 490x590 |
Thickness | mm | 50 | 50 | 50 | 50 | 50 | 50 | 50 |
* Based on an indoor air temperature of 27°C de dry bulb and 19°C wet bulb. Inlet water temperature 7°C , water temperature difference 5K and nominal air flow. ** Based on an indoor air temperature of 20°C dry bulb. Inlet water temperature of 70°C , water temperature difference 10K and nominal air flow. *** Based on an indoor air temperature of 20°C dry bulb. Inlet water temperature 45°C , water temperature difference 5K and nominal air flow.