The fancoil FCY-EC concept extends to non residential applications where the demands of thermal capacity, robustness, reliability and efficiency requirements prevail over product customization.
The FCY-EC range is presented as a big solution in terms of thermal capacity, which allows the designer to find in only one device the performance of several conventional fancoils. Its configuration with EC fans is an advantage not only for contrabillity besides it provides a high performance with a sound comfort. Thus, this product range is an economical, reliable solution with a plus adaptive features suitable for several sectors.

This product range offers reliable solutions from 4000 to 13000 m3/h, mainly for secondary air handling. Its possible compatibility with hydronic and direct expansion systems makes it a versatile product, suitable for any installation, regardless of the type of production.
The regulation of the fan working in variable flow, constant flow or multi-velocity systems is a fact with EC fans, providing to the unit the necessary autonomy and reducing maintenance to a minimum.
FCY-EC range features stem from a culture of reliable product development, reflecting the know-how of years of experience and knowledge of HVAC market in a series that stands out for its robustness and good performance.

EC Technology
The EC technology has a significant high efficiency (level IE4). Integrating rotor, motor and electronics are adjusted to obtain optimum results.

Adaptability and Robustness
FCY-EC components that are widely tested in the market, the available configurations and also adaptability offered, make this unit a versatile and robust solution.

Economy
The FCY-EC series has been fully optimised, both in terms of design and component selection. This has resulted in a range that stands out for its high performance-price ratio.

Comprehensive Solution
FCY-EC product range offers a comprehensive solution for customer and installer. The possibility of regulating the operating point of the fan and integrated thermostat control make this a comfortable and compact solution.

Technical Characteristics
FCY-EC | 018 | 025 | 030 | 040 | 045 | 055 | 075 | |||||
Nominal Cooling Capacity * | kW | 19 | 28 | 32 | 41 | 60 | 66 | 81 | ||||
Nominal Heating Capacity ** | kW | 51 | 64 | 72 | 93 | 132 | 143 | 175 | ||||
Nominal Heating Capacity *** | kW | 25 | 32 | 36 | 46 | 65 | 71 | 87 | ||||
Weight | kg | 130 | 140 | 150 | 230 | 297 | 317 | 365 | ||||
Exchanger water/air | ||||||||||||
Frontal Area | m² | 0,550 | 0,638 | 0,696 | 0,84 | 1,098 | 1,098 | 1,338 | ||||
Nº Rows…Fins/m | 4...476 | 4...500 | 4...500 | 4...500 | 6...476 | 6...476 | 6...476 | |||||
Manifold | pulg | 1 1/4" | 1 1/4" | 1 1/4" | 1 1/2" | 2" | 2" | 2" | ||||
Water Volume | l | 5,5 | 6,4 | 7 | 8,4 | 16,5 | 16,5 | 20,2 | ||||
Water Flow (Cold Coil) | l/h | 2900 | 4800 | 5700 | 7000 | 10100 | 11300 | 13400 | ||||
Water Flow (Heat Coil) ** | l/h | 4500 | 5600 | 6300 | 8100 | 11600 | 12500 | 15300 | ||||
Water Flow (Heat Coil) *** | l/h | 4400 | 5500 | 6200 | 8000 | 11400 | 12300 | 15100 | ||||
Pressure Drop_Water (Cold Coil) | kPa | 7.6 | 17.2 | 20.4 | 30.4 | 16.4 | 20 | 31.8 | ||||
Pressure Drop_Water (Heat Coil) ** | kPa | 13.6 | 18 | 18.9 | 34.5 | 17.8 | 20.5 | 34.8 | ||||
Pressure Drop_Water (Heat Coil) *** | kPa | 14.4 | 19.1 | 20.1 | 36.8 | 19 | 21.9 | 37.3 | ||||
Fan | ||||||||||||
Air Flow | m³/h | 4300 | 5364 | 6084 | 7884 | 9504 | 10476 | 12708 | ||||
Quantity | ud. | 1 | 1 | 1 | 1 | 1 | 1 | 2 | ||||
External Pressure | Pa | 200 | 200 | 220 | 220 | 240 | 240 | 260 | ||||
Maximum External Pressure | Pa | 572 | 710 | 442 | 570 | 595 | 923 | 763 | ||||
Motor | ||||||||||||
Quantity | 1 | 1 | 1 | 1 | 1 | 1 | 2 | |||||
Power | W | 1650 | 2250 | 1850 | 2730 | 3510 | 5500 | 2x3000 | ||||
Air Filtration | ||||||||||||
Quantity | 2 | 2 | 2 | 2 | 1 | 2 | 1 | 2 | 1 | 3 | 1 | |
Wide x Height | mm | 590x490 | 590x540 | 590x590 | 590x590 | 290x590 | 590x590 | 690x590 | 590x590 | 690x590 | 590x590 | 490x590 |
Thickness | mm | 50 | 50 | 50 | 50 | 50 | 50 | 50 |
* Based on an indoor air temperature of 27°C dry bulb and 19°C wet bulb. Inlet water temperature 7°C , water temperature difference 5K and nominal air flow. ** Based on an indoor air temperature of 20°C dry bulb. Inlet water temperature of 70°C , water temperature difference 10K and nominal air flow. *** Based on an indoor air temperature of 20°C dry bulb. Inlet water temperature 45°C , water temperature difference 5K and nominal air flow.